Frozen evaporator coil
- Points to it
- Vent airflow becomes weak, the larger insulated copper line is frosted, or water appears near the indoor unit after cooling is switched off.
- Rules it out
- Strong airflow and a dry, ice-free line make a severe freeze-up less likely, although ice can remain hidden inside the indoor cabinet.
Low airflow or abnormal refrigerant pressure can pull the coil below freezing. Ice then blocks more airflow and the problem feeds itself. Continued cooling can spread ice and strain the compressor. Set cooling to OFF, use fan ON if the blower sounds normal, and allow a full thaw. A technician still needs to identify why it froze.
Clogged filter or blocked airflow
- Points to it
- The filter is packed with dust, vents are closed, the return is blocked, or airflow weakened gradually while the system ran longer.
- Rules it out
- A clean, correctly sized filter with open vents and a clear return makes household restrictions less likely, but does not rule out a dirty coil or blower problem.
Restricted airflow keeps warm room air from crossing the evaporator. The coil can fall below freezing while the house stays warm. Replace a dirty filter and open vents. If ice is present, keep cooling off until everything thaws. Restarting too soon can freeze it again.
Outdoor unit not running
- Points to it
- The indoor fan moves room-temperature air, but the outdoor unit is completely silent during a cooling call: no hum, no click, no fan.
- Rules it out
- A steady outdoor fan and normal compressor sound make a total shutdown less likely, but do not prove the system is moving heat correctly.
If the outdoor section loses power or a component fails, the indoor blower can keep circulating warm air. Confirm the breaker and disconnect only. Never reach through the grille, remove a panel, or start the fan by hand. A silent or humming unit needs electrical diagnosis.
Failed capacitor or contactor
- Points to it
- The outdoor unit clicks or hums without starting, starts intermittently, or stops shortly after trying while the indoor blower runs.
- Rules it out
- A normal outdoor start makes a completely failed capacitor or contactor less likely during that cycle, but does not eliminate a weakening part.
The capacitor helps motors start and run, while the contactor switches power outdoors. Failure can leave a compressor or fan energized without starting, adding heat and strain. Switch cooling off and leave the cabinet closed. A technician tests these parts because a capacitor can hold a charge after the power is off.
Low refrigerant from a leak
- Points to it
- Cooling faded over time, the insulated line or coil freezes, long runs continue, and replacing the filter does not restore cooling.
- Rules it out
- Normal refrigerant measurements on a clean, thawed system rule it out. Appearance and touch alone cannot confirm charge.
Refrigerant is not consumed in normal operation, so a low charge means it escaped. Low pressure can pull the evaporator below freezing and reduce heat transfer. Adding refrigerant without locating the leak is temporary. After a full thaw, system readings confirm the condition and guide leak repair.
Thermostat or control-wiring fault
- Points to it
- The display is blank, changes unexpectedly, calls for cooling when one section does not respond, or works intermittently after a power interruption.
- Rules it out
- A thermostat that consistently starts both indoor and outdoor equipment makes complete control failure less likely, although a loose connection can be intermittent.
The controls coordinate the blower, outdoor fan, and compressor. A failed thermostat, safety switch, transformer, or connection can leave only part operating. Homeowner checks stop at the display, mode, setpoint, breaker, and drain pan. Do not handle wires. A technician traces the control signal safely.